HID Protocol
For UPS
Table 1: Power Device Physical Units Implemented in HID Units
| -------------- | Physical Unit | HID Unit | HID Unit Code | HID Unit Exponent | HID Size |
|---|---|---|---|---|---|
| AC Voltage | Volt | Volt | x00F0D121 | 7 | 8 |
| AC Current | centiAmp | Amp | x00100001 | -2 | 16 |
| Frequency | Hertz | Hertz | xF001 | 0 | 8 |
| DC Voltage | centiVolt | Volt | x00FOD121 | 5 | 16 |
| Time | second | s | x1001 | 0 | 16 |
| DC Current | centiAmp | Amp | x00100001 | -2 | 16 |
| Apparent or Active Power | VA or W | VA or W | xD121 | 7 | 16 |
| Temperature | °K | °K | x00010001 | 0 | 16 |
| Battery Capacity | AmpSec | AmpSec | x00101001 | 0 | 24 |
| None | None | None | x0 | 0 | 8 |